set_mode_analog_output (Manual Mode)

This section explains how to use set_mode_analog_output during Manual (Teach) operations to configure the signal type (Voltage or Current) of the control box analog output channels.

Typical usage

  • Select whether each analog output channel outputs voltage (0–10 V) or current (4–20 mA) signals.

  • Match the robot’s analog output mode with the connected device (e.g., inverter, proportional valve).

  • Adjust analog signal mode before sending values via set_analog_output.

Note

Example: Configure analog output modes

#include "DRFLEx.h"
#include <cstdio>
using namespace DRAFramework;

int main() {
    CDRFLEx drfl;

    // Preconditions:
    // - Connection established (open_connection)
    // - Manual (Teach) mode active

    // 1) Set CH1 output mode to voltage (0–10 V)
    drfl.set_mode_analog_output(ANALOG_OUT_CH1, GPIO_ANALOG_TYPE_VOLTAGE);
    std::printf("[Analog OUT CH1] Mode set to VOLTAGE\n");

    // 2) Set CH2 output mode to current (4–20 mA)
    drfl.set_mode_analog_output(ANALOG_OUT_CH2, GPIO_ANALOG_TYPE_CURRENT);
    std::printf("[Analog OUT CH2] Mode set to CURRENT\n");

    return 0;
}

Tips

  • Match the target device’s expected input type before enabling analog output.

  • For voltage mode, ensure total load impedance is ≥ 10 kΩ; for current mode, ensure ≤ 500 Ω.

  • Incorrect mode selection can cause distorted or unstable output signals.

  • Reconfigure mode after reboot if settings are not stored persistently.